Best-Selling 12 Kv Transformer Substation - S13 Series Of Oil-Immersed Transformer – Pengbian
Best-Selling 12 Kv Transformer Substation - S13 Series Of Oil-Immersed Transformer – Pengbian Detail:
Types of meaning

S13-M series 10 kv three-phase double winding excitation regulating distribution transformer
|
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
|
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
|
30 |
6 6.3 6.6 10 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yzn11 Yyno |
80 |
630/660 |
1.2 |
4.0 |
|
50 |
100 |
910/870 |
1.0 |
|||||
|
63 |
110 |
1090/1040 |
0.95 |
|||||
|
80 |
130 |
1310/1250 |
0.95 |
|||||
|
100 |
150 |
1580/1500 |
0.90 |
|||||
|
125 |
170 |
1890/1800 |
0.90 |
|||||
|
160 |
200 |
2310/2200 |
0.80 |
|||||
|
200 |
240 |
2730/2600 |
0.80 |
|||||
|
250 |
290 |
3200/3050 |
0.70 |
|||||
|
315 |
340 |
3830/3650 |
0.70 |
|||||
|
400 |
410 |
4520/4300 |
0.65 |
|||||
|
500 |
480 |
5410/5150 |
0.65 |
|||||
|
630 |
Dyn11 Yyno |
570 |
6200 |
0.45 |
4.5 |
|||
|
800 |
700 |
7500 |
0.45 |
|||||
|
1000 |
830 |
10300 |
0.45 |
|||||
|
1250 |
970 |
12000 |
0.40 |
|||||
|
1600 |
1170 |
14500 |
0.40 |
|||||
|
2000 |
1550 |
18300 |
0.30 |
5.0 |
||||
|
2500 |
1830 |
21200 |
0.30 |
|||||
e: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of the load loss value applies to Yyno link group.
S13-M series of 20 kv three-phase double winding non-field excitation changer distribution transformer
|
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
|
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
|
30 |
20 22 24 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yzn11 Yyno |
80 |
690/660 |
2.1 |
5.5 |
|
50 |
100 |
1010/960 |
2 |
|||||
|
63 |
110 |
1200/1150 |
1.9 |
|||||
|
80 |
130 |
1440/1370 |
1.8 |
|||||
|
100 |
150 |
1730/1650 |
1.6 |
|||||
|
125 |
170 |
2080/1980 |
1.5 |
|||||
|
160 |
200 |
2540/2420 |
1.4 |
|||||
|
200 |
240 |
3000/2860 |
1.3 |
|||||
|
250 |
290 |
3520/3350 |
1.20 |
|||||
|
315 |
340 |
4210/4010 |
1.10 |
|||||
|
400 |
410 |
4970/4730 |
100 |
|||||
|
500 |
480 |
5940/5660 |
1.00 |
|||||
|
630 |
570 |
6820 |
0.90 |
6.0 |
||||
|
800 |
700 |
8250 |
0.80 |
|||||
|
1000 |
830 |
11330 |
0.70 |
|||||
|
1250 |
970 |
13200 |
0.70 |
|||||
|
1600 |
1170 |
15950 |
0.60 |
|||||
|
2000 |
1550 |
19140 |
0.60 |
|||||
|
2500 |
1830 |
22220 |
0.50 |
|||||
S13-M series of 35 kv three-phase double winding non-field excitation changer distribution transformer
|
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
|
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
|
50 |
35 38.5 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
130 |
1200/1140 |
1.05 |
6.5 |
|
100 |
185 |
2010/1910 |
0.90 |
|||||
|
125 |
215 |
2370/2260 |
0.90 |
|||||
|
160 |
225 |
2820/2680 |
0.80 |
|||||
|
200 |
270 |
3320/3160 |
0.80 |
|||||
|
250 |
320 |
3950/3760 |
0.75 |
|||||
|
315 |
380 |
4750/4530 |
0.75 |
|||||
|
400 |
460 |
5740/5470 |
0.65 |
|||||
|
500 |
540 |
6910/6580 |
0.65 |
|||||
|
630 |
660 |
7860 |
0.50 |
|||||
|
800 |
780 |
9400 |
0.50 |
|||||
|
1000 |
920 |
11500 |
0.50 |
|||||
|
1250 |
1120 |
13900 |
0.45 |
|||||
|
1600 |
1350 |
16600 |
0.45 |
|||||
|
2000 |
1590 |
19700 |
0.40 |
|||||
|
2500 |
1890 |
23200 |
0.40 |
|||||
Note: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of the load loss value applies to Yyno link group.
Product detail pictures:
Related Product Guide:
Cooperation
The customer satisfaction is our primary target. We uphold a consistent level of professionalism, quality, credibility and service for Best-Selling 12 Kv Transformer Substation - S13 Series Of Oil-Immersed Transformer – Pengbian , The product will supply to all over the world, such as: Greece , Detroit , Surabaya , We will not only continuously introduce technical guidance of experts from both home and abroad, but also develop the new and advanced products constantly to satisfactorily meet the needs of our clients all over the world.
We feel easy to cooperate with this company, the supplier is very responsible, thanks.There will be more in-depth cooperation.